  • Equipment - BACnet - York - York RTU BACnet Setup Guide

Equipment - BACnet - York - York RTU BACnet Setup Guide

Written by Brian Matheron

Updated at May 29th, 2026

Table of Contents

BACnet Configuration Steps MS/TP Wiring Requirements Integration Notes (GPEC / GEM) Common Issue

Required configuration steps for York RTUs to ensure proper BACnet MS/TP communication and control with EMS platforms (ex: GPEC / GEM).

BACnet Configuration Steps

  •  Access the RTU controller via onboard display inside the unit
  • Navigate to: MENU - COMMUNICATIONS - BAS / PROTOCOL
  • Set Protocol to BACnet MS/TP
  • Set Baud Rate to 19200 (use 38400 only if required)
  • Assign unique MAC Address (recommended: 5–9 if controller is 4)
  • Set BACnet Device Instance (must be unique across network)
  • Save configuration and exit menu
  • Power cycle unit
  • Access onboard York controller again to verify settings were retained

MS/TP Wiring Requirements

  • Use daisy chain protocol
  • Maintain wiring polarity through whole trunk
  • Install 120-ohm termination resistor at first and last device
  • Ensure consistent baud rate across all devices (19200 or 38400)
  • Avoid duplicate MAC addresses or Device IDs

Integration Notes (GPEC / GEM)

  • Recommended addressing: GPEC = 4, RTUs = 5–9
  • Use BACnet_2 (RS485 Port #2)
  • Ensure MAC Address and Device ID match GEM configuration
  • Avoid BACnet_3 unless manually configured

Common Issue

  • Intermittent comms: verify baud rate, EOL resistors, and addressing

Did you find this article helpful?

Yes
No

More Information

  • Equipment - BACnet - Carrier & York Setup with Single EC2000