Equipment - BACnet - York - York RTU BACnet Setup Guide
Table of Contents
Required configuration steps for York RTUs to ensure proper BACnet MS/TP communication and control with EMS platforms (ex: GPEC / GEM).
BACnet Configuration Steps
- Access the RTU controller via onboard display inside the unit
- Navigate to: MENU - COMMUNICATIONS - BAS / PROTOCOL
- Set Protocol to BACnet MS/TP
- Set Baud Rate to 19200 (use 38400 only if required)
- Assign unique MAC Address (recommended: 5–9 if controller is 4)
- Set BACnet Device Instance (must be unique across network)
- Save configuration and exit menu
- Power cycle unit
- Access onboard York controller again to verify settings were retained
MS/TP Wiring Requirements
- Use daisy chain protocol
- Maintain wiring polarity through whole trunk
- Install 120-ohm termination resistor at first and last device
- Ensure consistent baud rate across all devices (19200 or 38400)
- Avoid duplicate MAC addresses or Device IDs
Integration Notes (GPEC / GEM)
- Recommended addressing: GPEC = 4, RTUs = 5–9
- Use BACnet_2 (RS485 Port #2)
- Ensure MAC Address and Device ID match GEM configuration
- Avoid BACnet_3 unless manually configured
Common Issue
- Intermittent comms: verify baud rate, EOL resistors, and addressing