Equipment - Meters - 1204EX - Meter Offline
This article will guide you through troubleshooting an offline 1204EX meter.
Table of Contents
Power Steps
- Turn on breaker supplying 120 VAC.
 - Measure voltages across TS2 terminals.
 - Check for loose connections on TS2 terminals.
 - Set JMP1 switch to appropriate voltage setting for the site. 
- Most US sites will be 115 VAC
 - Check for lights 
- If no, transformer may be blownSet JMP1 switch to appropriate voltage setting.
 
 
 


Communication Steps
- Check wiring for the RS-485. 
- Make sure wires aren’t stripped for punch-downs.
 - Check on 1204EX and at HUB, IOM, or controller connecting to 1204EX.
 
 - Check address setting. 
- Starts at 0 and goes to 9
 - If having trouble finding address, set it to every address and see what you get.
 - If you change address, hit reset switch.
 
 - Reset the 1204-EX using the reset switch near the RS-485 Communication Board.
 
- If the “No” switch is set to down, switch it to up.
 

- Confirm programming.
 - Replace 1204-EX.