  • Equipment – Thermostats – TS150W – Inaccurate Temperature Readings

Equipment – Thermostats – TS150W – Inaccurate Temperature Readings

This article will guide you through troubleshooting inaccurate temperature readings with a TS150W thermostat.

Written by Brian Matheron

Updated at January 26th, 2026

Table of Contents

Inaccurate Temperature Readings

Inaccurate Temperature Readings

  • Locate the TS150W Thermostat.
  • Determine whether the temperature in question is being read by a ZSM associated to the thermostat or the thermostat itself.
    • If the temperature is being read by the ZSM, review this article Equipment - ZSM - Troubleshooting Inaccurate Tasseron ZSM Temperature.
    • To change the control strategy, open the Information tab on the TS150W asset in GridPoint Intelligence.
    • Scroll to the bottom. Click Edit Control Strategy.
    • Determine if you want a Single or Average control strategy.
      • For single, select the controlling device.
      • For average, select all devices to average.
    • Click Save.
  • If it is the thermostat temperature reading, breathe on the sensor to see if the temperature fluctuates. Test the reporting temperature against a thermometer in the same exact spot.
  • If the temperature fails to fluctuate or continues to read incorrectly, power cycle (disconnect power supply and reconnect after thirty seconds) and check the reported temperature.
  • If it continues to report incorrectly, contact GridPoint Support for more details.

 

Did you find this article helpful?

Yes
No

More Information

  • Equipment – Thermostats – TS150W – Fan Issues
  • Equipment – Thermostats – TS150W – Heating Issues
  • Equipment – Thermostats – TS150W – Device Offline
  • Equipment – Thermostats – TS150W – Inaccurate Humidity Readings

See More On

faulty readings temperature inaccuracies ts150w wireless